How do I size the fire water storage tank for a high-rise building?
The fire water storage tank is sized according to the sprinkler or standpipe demand, whichever is larger for the water supply duration as stated in NFPA 13 table 11.2.3.1.2
The fire water storage tank is sized according to the sprinkler or standpipe demand, whichever is larger for the water supply duration as stated in NFPA 13 table 11.2.3.1.2
Maximum two residential heads shall be hydraulically calculated for the design criteria listed in section 10.2.1 of NFPA 13D.
Storage tanks for fire protection are required for new high-rise buildings over 75 ft. and for existing building falling under the scope of chapter 86 of LABC when the building height exceeds 150 ft.
The maximum pressure in the sprinkler system shall not exceeds 350 PSI at any location in the system. Sprinkler systems can be zoned to avoid exceeding such pressure.
Floor control valves and waterflow detection assemblies shall be installed at each floor where any of the following occur:
A master PRV is allowed to be installed downstream of a fire pump when a second master PRV is installed to provide redundancy, so that failure of one PRV does not affect the operation of the fire protection system.
The flow and pressure requirements are 250 GPM at 100 PSI when PRV is not required, and 250 GPM at 125 PSI when PRV is required.