Floor control valves and waterflow detection assemblies shall be installed at each floor where any of the following occur:

  1. Buildings where the floor level of the highest story is located more than 30 feet above the lowest level of fire department vehicle access
  2. Buildings that are four or more stories in height
  3. Buildings that are two or more stories below the highest level of fire department vehicle access



     