Mechanical HVAC Permits
Mechanical HVAC Permits are required for any installation or modification of heating/cooling systems, smoke control systems, hood and ventilation systems, or engineered water heater/heating appliance vents.
About Mechanical HVAC Permits
Plans shall be filed with and approved by the Department (as an HVAC Plan Check) before any permit is issued for work listed below is started:
- Installations where the aggregate BTU/H input capacity is 500,000 BTU/H (2299.3 L/W) and over, for comfort heating, or for comfort-cooling, or for absorption units for commercial applications
- Installations where the system BTU/H input capacity is 500,000 BTU/H (2299.3 L/W) and over for comfort heating, or for comfort cooling, or for absorption units for residential applications
- Smoke-control systems
- Any comfort-cooling compressor or refrigeration compressor for any system which contains any Group B refrigerant
- Any commercial cooking hood and ventilation system
- Product conveying ventilation systems
- Engineered water heater/heating appliance vents
For more information on the Plan Check process, visit our Express Permit, Regular Plan Check and Counter Plan Check pages.
Additional Resources
- Code Amendment
- Forms & Applications
- Information Bulletins
- Standard Correction Lists
Filtered categories:
Supplemental Plan Check Corrections Sheet for Fire District 1 and Very High Fire Hazard Severity Zone (2020 LABC)
PC/STR/Corr.Lst.109-2020
Swimming Pools Plan Check Correction Sheets (2020 LABC)
PC/STR/Corr.Lst.108-2020
Supplemental Plan Check Correction Sheet for Two-way Concrete Slab (2023 LABC)
PC/STR/Corr.Lst.045-2023
Supplemental Plan Check Correction Sheet for Steel Moment Frame Design (2020 LABC)
PC/STR/Corr.Lst.052-2020
Supplemental Plan Check Correction Sheet for Sound Transmission (2020 LABC)
PC/STR/Corr.Lst.105-2020
Supplemental Plan Check Correction Sheet for Office of Statewide Health and Planning Department (OSHPD) Requirements (2020 LABC)
PC/STR/Corr.Lst.113-2020
Supplemental Plan Check Correction Sheet for Security Requirements (2020 LABC)
PC/STR/Corr.Lst.103-2020
Supplemental Plan Check Correction Sheet for Masonry Wall Design (2020 LABC)
PC/STR/Corr.Lst.042-2020
Supplemental Plan Check Correction Sheet for Methane Seepage Regulations (2023 LABC)
PC/STR/Corr.Lst.055-2023
Filtered categories:
What I need to do in order to change the model designation, or other non-technical changes to my approval?
What I need to do to maintain my approval if I modify my equipment during the approval period?
Filtered categories:
Examination Info Boiler Operator and Steam Engineer
IB/P/PVC 2024-001
Exams for Specialties Regulated Under Chapter 9 of the Los Angeles Municipal Code
IB/P/BC 2020-072
- Effective
Exemptions from Liquefaction, Earthquake Induced Landslide, and Fault-rupture Hazard Zone Investigations
IB/P/BC 2023-044
- Effective
Exemptions from Liquefaction, Earthquake Induced Landslide, and Fault-rupture Hazard Zone Investigations
IB/P/BC 2017-044
- Effective
Existing Escalator Clearance Between the Skirt and the Step
IB/P/EV 2002-001
- Effective
Exit illumination and Exit Sign Lighting Systems
IB/P/BC 2023-019
- Effective